Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2003 |
ELECTRIC - FINAL |
|
Approved |
SENT TO TEP ON 0923AM |
| 08/04/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) SERVICE UPGRADED TO 60 AMPS, HOWEVER IT HAS AN EXISTING 60 AMPS 2 POLE EXISTING, 30 AMPS 2 POLE DRYER, 4 - 20 AMPS 1 POLE BREAKERS. THE EXISTING 60 AMP IS TOO SMALL, YOU ALSO NEED A PERMIT FOR THIS TYPE OF WORK. 2) BEDROOMS ARE REQUIRED TO HAVE SMOKE DETECTORS. 3) STORAGE ROOM LOCKED. |
| 08/01/2003 |
ELECTRIC - FINAL |
|
Denied |
|
| 07/18/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) DISCONNECTS OUTSIDE AT SERVICE HAVE DOUBLE TAPS ON LOAD SIDE, IN VIOLATION OF N.E.C. 110-3. 2) RECEPTACLE BOX AND COVER FOR A/C UNIT NOT WEATHER PROOF. 3) INSTALL MISSING PLATES INSIDE FOR RECEPTACLES, SWITCHS. 4) DISCONNECT SWITCHES ARE NOT OUTDOOR RATED AND SHOULD BE CHANGED. USE LICENSED CONTRACTOR, OBTAIN PERMITS NECESSARY FOR SERVICE MODIFICATIONS. |