Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/30/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 07/23/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) BOND GAS PIPING. 2) INSTALL PERMANANT ADDRESS LABEL. MUST BE SCREWED OR RIVITED TO ENCLOSURE. 3) INSTALL BOND BUSHING WHERE USING RE-WASHERS, 3/4" CONDUIT CON. 4) STRAP GROUND WIRE TO WALL OF HOUSE. RECALL WHEN DONE. |