Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL01380

Parcel: 119211020


Addresses:

1601 W CIRCLE A DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/30/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
07/23/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ 1) BOND GAS PIPING. 2) INSTALL PERMANANT ADDRESS LABEL. MUST BE SCREWED OR RIVITED TO ENCLOSURE. 3) INSTALL BOND BUSHING WHERE USING RE-WASHERS, 3/4" CONDUIT CON. 4) STRAP GROUND WIRE TO WALL OF HOUSE. RECALL WHEN DONE.