Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 08/21/2003 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 08/22AM |
| 08/13/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0210*/ 1) THE RISER CONDUIT, ABOVE THE ROOF, NEEDS A BRACE. 2) THE RISER CONDUIT NEEDS TWO STRAPS BETWEEN BOX AND EAVES. THE FIRST STRAP MUST BE LOCATED WITHIN 8" OF THE BOX. DO NOT ATTACH TO THE BIRD/FRIESE BOARD AT THE TOP. THESE BOARDS ARE NON STRUCTURAL. 3) ATTACH A PERMANENT ADDRESS LABEL BELOW THE METER. PENCIL, PEN, OR MAGIC MARKER ARE NOT ALLOWED. 4) ADD A MIN.OF TWO STRAPS TO THE GROUNDING WIRE AT THE SIDE OF HOUSE NEAR WATER PIPE. 5) INSTALL ADDRESS #'S AT FRONT OF HOUSE. SEE PIMA COUNTY ADDRESS REQUIREMENTS SHEET. 6) PROVIDE PROOF THAT RISER WIRES ARE SUNLIGHT RESISTANT. CORRECT AND RECALL. |