Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*/ 1) CALLED CLEARANCE IN 1:10 PM |
| 08/01/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) NOTES: 1) (2) GROUND RODS REQUIRED 6' MINIMUM APART, USE UNSPLICED GROUND WIRE, PER ART 250 NEC. 2) BOND WATER PIPING 3) ID CIRCUIT BREAKERS 4) INSTALL PERMANENT ADDRESS LABEL 5) STRAP GROUND WIRE TO WALL 6) USE APPROVED CONDUIT STRAP |