Permit: T03EL01324

Parcel: 117091310


Addresses:

1121 S 8TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/05/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*/ 1) CALLED CLEARANCE IN 1:10 PM
08/01/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ 1) NOTES: 1) (2) GROUND RODS REQUIRED 6' MINIMUM APART, USE UNSPLICED GROUND WIRE, PER ART 250 NEC. 2) BOND WATER PIPING 3) ID CIRCUIT BREAKERS 4) INSTALL PERMANENT ADDRESS LABEL 5) STRAP GROUND WIRE TO WALL 6) USE APPROVED CONDUIT STRAP