Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2003 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*/ 1) SERVICE UPGRADE IS COMPLETE. PLEASE VERIFY NEW A/C PERMIT | |
| 07/11/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1) ADDRESS ON SERVICE MUST B OF A PERMENENT TYPE NO MARKER. 2) GROUND RODS TO BE DRIVEN FLUSH TO GRADE AS TO NOT POSE TRIP HAZARD. 3) NEUTRAL OFF 100 A CB FEEDER TO BE TAPED WHITE. 4) NO PERMIT FOR NEW A/C. 5) NEED A MAIN BONDING JUMPER FROM NEUTRAL BAR TO GROUND BAR BECAUSE UFER JUST TIED TO GROUND BAR. 6) LABEL OR MARK CIRCUIT BREAKER USE. 7) WHO IS ELECT CONTR.. ONE IS REQUIRED SINCE HOUSE IS VACANT. LEAVE THIS COPY ON SITE FOR NEXT INSP |