Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/07/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* 1) SMOKE DETECTORS REQUIRED IN EACH BEDROOM 2) EXPOSED WIRING BELOW 8' MUST BE IN CONDUIT, STORGE AREA IN BACK. 3) UNIT MUST HAVE WORKING HEATING AND COOLING 4) SERVICE IS OLD AND OUTDATED, CONDUITS NOT SUPPORTED, PARTS MISSING, IMPROPERLY GROUNDED IN NEED OF REPAIR OR REPLACEMENT. WORK MUST BE DONE BY LICENSED CONTRACTOR WITH PROPER PERMITS IF NECESSARY FOR REPLACEMENT. RE-CALL FOR INSPECTION WHEN READY. 5) UNIT # TO BE INSPECETED MUST BE ON PERMIT A, B OR C |