Permit: T03EL01304

Parcel: 115081020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 0904AM
08/27/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0210*/ CORRECTIONS REQUIRED: 1) THE GAS BOND MUST BE TERMINATED ON THE HOUSE SIDE PIPING. CLEAN THE PAINT OFF BEFORE ATTACHING THE CLAMP. 2) THE MAIN GROUNDING CONDUCTOR MUST TERMINATE ON THE NEUTRAL BAR OF EACH MMLC. RE-ROUTE. 3) EXAMPLE DIAGRAM ON PAPER COPY SHOWS THESE MAY BE SHORT JUMPERS RUN BETWEEN PANELS. CORRECT AND RECALL. LEAVE GUTTER COVER OFF FOR INSPECTION.