Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/03/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 01/28/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 01/21/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) A MANUFACTURERS HOLDOWN IS NEEDED FOR BACK FEED BREAKER 584.16 2) LUGS CANNOT BE STACKED 3) CLEAR SURFACE UNDER LUGS AND USE FULL CONTACT TO SURFACE LUGS 4) WE HAVE MULTIPLE TERMINATIONS AT LUG 5) JUNCTION BOX TO BE GROUNDED 6) PLANS NEED BE REVISED TO REFLECT WORK INSTALLED OR INSTALL AS PER PLANS |