Inspection History: ELECTRIC - FINAL

Permit Number - T03EL01242

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/18/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK ON INTERIOR 2) MEET WITH ELECTRICAL CONTRACTOR AND OWNER 3) PLEASE FINISH #1-5 AND 7 OF PREVIOUS INSPECTION
08/13/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) USE APPROVED FITTING AT LB. CHASE NIPPLE NOT APPROVED 2) PANEL AT 2ND STRUCTURE TO HAVE MAIN DISCONNECTING MEANS 3) BREAKERS TO BE LABELED 225.31 AND 225.32 4) BOND JUNCTION BOX ENCLOSURE 250.148 5) SERVICE DISCONNECTING MEANS IN DELAPADATED CONDITION UPGRADE TO CODE-NEW PERMIT REQUIRED 6) UNIT LOCKED-NEED ACCESS TO INTERIOR 7) PLEASE VERIFY GAS BONDING 250.104
07/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ WHO IS LICENSED ELECTRICAL CONTRACTOR? NO FURTHER INSPECTIONS UNTIL WE HAVE A LICENSED ELECTRICAL CONTRACTOR FOR JOB. PLEASE HAVE CONTRACTOR CALL ME : PAGER 218-0204.
06/25/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) AN ADDRESS IS TO BE POSTED OUT ON UNIT. 2) WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM. 3) PLEASE PROVIDE A SMOKE DETECTOR 4) SERVICE IS IN AN DELAPIDATED CONDITION. 5) HAVE A LICENSED ELECTRICAL CONTRACTOR PERFORM WORK TO BE DONE. 6) WE HAVE UNSAFE WIRING IN BATHROOM