Permit: T03EL01241

Parcel: 127031140


Addresses:

5719 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/10/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR
07/09/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0910*/PLEASE LOCK UP DOG.
06/27/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 2) A GAS AND WATER BOND ARE NEEDED 3) MAINTAIN WORKING CLEARACNES AT SERVICE 110.26 4) LABEL BREAKER 5) IDENTIFY NEUTRAL AT WEATHER HEAD 6) WE HAVE MULTIPLE TERMINATIONS AT GROUND BAR