Permit: T03EL01234

Parcel: 117082740


Addresses:

925 S RAILROAD AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/25/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) REPLACE RECEPTACLE / SWIICH COMBO DEVICE IN KITCHEN ( BROKEN) 2) REPLACE SERVICE EQUIP. THE EXISTING SERVICE IS OUTDATED AND HAS WATER DAMAGE DUE TO THE USEOF INDOOR RATED EQUIP, USED OUTSIDE, EXPOSED TO WEATHER, OBTAIN NECESSARY PERMITS, USE C-11 LICENSED CONTR 3) REPAIR PHONE CABING IN BACK THAT IS HANGING BETWEEN UNITS.