Permit: T03EL01217

Parcel: 124060490


Addresses:

1043 E 8TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03EL01217

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/28/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) REMOVE OVERHEAD RISER AND SEAL OPENING 2) SCREW COVER ON LB BELOW SERVICE
10/01/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0210*/ 1) THE LB CONTAINING UNFUSED SERVICE CONDUCTORS MUST BE SEALABLE. DRILL SMALL HOLE IN COVER TO LB BODY AT ANGLE TO ALL TEP TO ATTACH WIRE SEAL 2) RUN A GROUND WIRE BETWEEN PANEL NEUTRAL BARS. THE GROUND WIRE FROM 2 PIECE CLAMP TO 1043 E. PANEL IS NOT CORRECT AND THE CLAMP IS NOT MADE FOR TWO (2) WIRES
09/02/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
09/02/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*