Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/28/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) REMOVE OVERHEAD RISER AND SEAL OPENING 2) SCREW COVER ON LB BELOW SERVICE |
|
| 10/01/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0210*/ 1) THE LB CONTAINING UNFUSED SERVICE CONDUCTORS MUST BE SEALABLE. DRILL SMALL HOLE IN COVER TO LB BODY AT ANGLE TO ALL TEP TO ATTACH WIRE SEAL 2) RUN A GROUND WIRE BETWEEN PANEL NEUTRAL BARS. THE GROUND WIRE FROM 2 PIECE CLAMP TO 1043 E. PANEL IS NOT CORRECT AND THE CLAMP IS NOT MADE FOR TWO (2) WIRES | |
| 09/02/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
| 09/02/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* |