Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK GROUND RODS 2) OLD SERVICE EQUIPMENT LISTED ON LABEL AS SERVICE EQUIPMENT ONLY. THIS CANNOT BE USED AS A SUB PANEL 3) PLEASE RECALL AFTER CROSS OVER |
| 06/23/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE DRIVE GROUND RODS CODE STATES 1ST HORIZONTAL 2) 2ND 45 DEGREE AND LAST 30" OF COVER-SHOW ? OF THIS ORDER, OK TO CLEAR |