Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL01175

Parcel: 122030190

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/06/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) AN APPROVED ? FITTING IS NEEDED 2) SPLICES TO BE TERMINATED 3) FILL UNUSED OPENING IN PANEL 4) PLEASE FINISH TERMINATION OFF ALL CONDUCTOR 5) THIS WORK TO BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR