Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL01156

Parcel: 107141300

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/01/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
06/30/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999$/ 1) YOUR MESSAGE STATES I DID NOT CALL YOU PRIOR TO INSPECTION ON 6/26/03, I LEFT A MESSAGE ON THE INSPECTION REPORT THAT I DID TRY TO CALL YOU AT 820-1092 BUT THERE WAS NO ANSWER. SAME TODAY I CALLED SAME NUMBER NO ANSWER. WRITE UP FROM 6/26/03 NOT TAKEN CARE OFF. PERMIT FOR A UNIT IS REQUIRED BEFORE I CAN CLEAR UNIT B-ALSO SEE CORRECTIONS
06/26/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) ONLY HAVE A REQUEST FOR ONE THIS PERMIT-YOU NEED TO HAVE A PERMIT FOR "A" ALSO AND CALL IN 2) NOTE TO ELECT-YOU ARE USING A GREEN COLORED WIRE AS A NEUTRAL AND EQUIPMENT GROUND-INSTALL A BLACK WIRE TAPED WHITE FOR THE NEUTRAL AND ISOLATE GROUNDS AND NEUTRALS IN SMALL J-BOXES