Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/12/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 09/11/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0920*/ LOCKED. PLEASE RECALL. |
| 09/02/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0920* LOCKED. NO ACCESS. |
| 08/12/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) HIGHEST AVAILABLE BREAKER NOT TO BE OVER 6'-7" 3) SEAL ENTRANCE ABOVE CURRENT CARRING PARTS 4) LABEL BREAKERS 5) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS AND VERIFY 2 GROUND RODS 6) PLEASE VERIFY GAS AND WATER BOND 7) CORRECTLY SUPPORT CONDUITS TO PANEL 8) IDENTIFY GROUNDED CONDUCTOR AT WEATHER HEAD 9) BONDING DEVICES NEEDED AT CONCENTRICS 10) HAVE CONTRACTOR CALL ME BEFORE NEXT INSPECTION 11) PROTECT CONDUCTORS ENTERING PANEL |