Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/14/2003 |
ELECTRIC - FINAL |
|
Approved |
1) LAST WRITE UP BY MAC CAPISTRAN COMPLETE-APPROVED 2) SENT TO TEP ON 7/15AM |
| 06/10/2003 |
ELECTRIC - FINAL |
|
Denied |
1) YOU NEED TO: SECURE AN ELECTRICAL SERVICE UPGRADE PERMIT FROM 100 AMP TO 200 AMP 2) INSTALL A COMPLETE NEW GROUNDING CIRCUIT CONSISTING TWO (2) 5/8" X 8' GROUND RODS, BONDING OF GAS AND WATER PIPING TO SERVICE PANEL, AND #4 BARE GROUND WIRE 3) A CIRCUIT DIRECTORY IN PANEL. 4) ALL WORK TO BE DONE BY A LICENSED ELECTRICAL CONTRACTOR |