Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/16/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210$/ 1) DENIED AS STATED ON LAST INSPECTION. A REINSPECTION FEE IN DUE BEFORE THE NEXT INSPECTION |
| 06/12/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*/ 1) PLEASE BOND TOGETHER THE GROUND AND NEUTRAL BAR 2) THE GAS BOND WIRE IS HAPHAZARDLY STREWN ABOUT ROOF TOP WITH OUT STRAPPING AND CROOKED THROUGHOUT. PLEASE SOLIDLY ATTACH TO THE CONTOUR OF THE WALL OR OTHER DIFFERENT WAY 3) NEED PERMANENT METAL ADRESS TAG 4) A REINSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION |
| 06/09/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0910*/ 1) PLEASE PROVIDE EXTENSION LADDER TO VIEW GAS GROUNDING CONDUCTORS AT TOP OF ROOF 2) NEED TO SEE A MAIN BONDING JUMPER BETWEEN EQUIPMENT GROUND BAR AND NEUTRAL BAR 3) NEED PERMANENT METAL ADDRESS TAG |