Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/23/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 06/18/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/1) ROCK TO BE 6' APART; 2) NEED GROUNDING BUSHINGS AND BONDING JUMPERS BETWEEN METER AND SERVICE PANEL BOARD; 3) STRAIGHTEN AND SECURE ALL CONDUITS 4) WIRE TO BE IN WEDGE OF ACORN CLAMP; 5) SECURE GROUND WIRE TO WALL; 6) NEED GAS BOND |
| 06/16/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0235*/ 1) IMPROPER GROUNDING 2) NEED GROUNDING BUSHINGS AND BONDING JUMPER THROUGH OUT 3) NEED 2 ROCK 4) CLAMPS FOR RODS-WIRE TO BE IN WEDGE 5) NEED PERMANENT ADDRESS TAG 6) NEED WATER AND GAS BOND 7) I SUGGEST THE IMPORTANCE OF OBTAINING A LICENSED CONTRACTOR TO PASS INSPECTION |