Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03EL01068
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
06/09/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) PLEASE PROVIDE ENGINEERED LOAD CALC'S FOR UNITS, UNITS APPEAR TO BE ALL ELECTRIC, 100 AMP SERVICE FOR EACH UNIT. MAY NOT BE ENOUGH CAPACITY. 50 AMP FOR RANGE, 40 AMP FOR AC UNIT, 30 AMP FOR WATER HEATER, 30 AMP FOR DRYER, 7-20 AMP FOR CONVIN. OUTLETS AND 4-15 AMP CONVIN. OUTLETS LIGHTING. SUPPORT 1 1/2" CONDUITS UP WALL WITHIN 3' OF TERMINATION |