Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/06/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 06/04/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) DRIVE GROUND RODS INTO GROUND 2) GROUNDING BUSHING AND BONDING JUMBPER ARE REQUIRED FOR ALL INTERVENING RACEWAYS/FITTINGS ON SUPPLY SIDE EQUIPMENT/HARDWARE 3) STACKING OF LUGS NOT PERMISSABLE AND REQUIRES NUT AND BOLTS CONNECTIONS 4) NEED MAIN BONDING JUMPER TO NEUTRAL BAR 5) WATER, GAS LINE AND TELEPHONE BOX SUBJACENT TO SERVICE EQUIPMENT VIOLATER NEC 110-26 6) REATTACH SERVICE TO WALL 7) GUTTER TERMINATION WILL BE TEP JURISDICTION |