Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/10/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) FOLLOW UP FOR CORRECTIONS 5 WORKING DAYS FOR INFORMATION CALL R.MAJUTA 909-5184 2) THE SEVICES ON THIS COMPLEX ARE IN NEED OF ATTENTION AND REPAIR. DUE TO OLD AGE. NO MAINTENCE TO SERVICE EQUIPMENT HAS GONE UN-ATTENDED A) THE GUTTER BELOW ROOF NEEDS TO BE CLEANED AND CLOSED PROPERLY B) ALL UNPROTECTED WIRING HAS BE BE PHYSICALLY PROTECTED TO 8' AFF C) OVER FUSING FOR ALL 20 AMP CIRCUITS PROTECED CORRECTLY D) PROPER ENTRY CLAMPS USED UNDER DISCONNECTS E) UNIT E IS ON BUT HANDLE OFF-IT'S IMPROPERLY WIRED INSIDE THE DISCONNECT, BUT FED THRU UNPROTECTED. ALL OF THESE ITMES POINT TO ELECTRICAL HAZARDS-HAVE A LICENSED ELECTRICAL CONTRACTOR CORRECT AS SOON AS POSSIBLE |
| 06/05/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) LOCKED OWNER NEEDED 1/2 BR-WAS ALREADY IN APPROX AREA-PLEASE RECALL AND LEAVE KEY IN DESIGNATED AREA AND LEAVE MESSAGE 2) CANNOT VERIFY CORRECTIONS 3) RICK TAKE A LOOK AT SERVICE D |