Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/30/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO CLEAR |
| 06/27/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CUSTOMERS BOYFRIEND IS DOING WORK 2) FINISH ITEMS #2, 4, 5 AND 7 OF PREVIOUS INSPECTION |
| 06/24/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) 2ND GROUND POD TO BE IN DEEP TRENCH WITH 30' OF COVER 2) WATER BOND TO BE TO ALL INTERIOR WATER PIPING 3) IDENTIFY GROUNDED CONDUCTOR AT PANEL AND JUNCTION BOX 4) BOND RISER 5) TIGHTEN SEAL TITE FITTINGS ON ROOF 6) GROUNDING EQUIPMENT CONDUCTOR IS NEEDED FOR SUB FEED ALSO BOX JUNCTION BOX ENCLOSURE 7) METER SOCKET WILL NEED TO BE REMOVED 8) PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR |