Permit: T03EL01044

Parcel: 128151060


Addresses:

5336 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/07/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
06/02/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) ROMEX CABLE IN FRONT OF HOUSE NEEDS TO BE IN CONDUIT WHERE EXPOSED UP WALL. RESUPPORT OUTSIDE LIGHT BY FRONT DOOR
05/30/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) FUSES AT FUSE BOX ARE TO LARGE (AMPS) FUSE ACCORDING TO WIRE SIZE #14 AWG-15 AMPS, #12 AWG 20 AMPS AND #10 AWG 30 AMPS 2) REMOVE EXTENSION CORD AT EXTERIOR . USED TO ENERGIZE FLOOD LIGHTS 3) YOU HAVE GROUNDING STYLE RECEPTACLES IN UNGROUNDED SYSTEM. CHANGE BACK TO 2 WIRE (WATECH PALARITY) OR CONSULT WITH A LICENSED CONTRACTOR