Permit: T03EL01007

Parcel: 133280770


Addresses:

8440 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/19/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
06/16/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) SUPPORT SEAL TITE AND CONDUIT ON SIDE OF PANEL 2) PLEASE IDENTIFY BREAKERS 3) IDENTIFY UNDERGROUND CONDUCTORS AS PER CODE 4) FINISH ITEM #2 OF PREVIOUS INSPECTION 5) RISER HARDWARE TO BE 1/4" MINIMUM 6) PLEASE CORRECT ADDRESS LABEL
06/06/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0920*