Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 06/14/2004 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection :* |
| 06/06/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*/ 1) A NEW GROUNDING ELECTRODE SYSTEM IS REQUIRED. NEED GAS AND WATER BOND. 2) NEED ALL G.E. BREAKER 3) TOP ENTRY REQUIRES SEALING FITTING 4) SUPPORT 3/4 CONDUIT, LOOSE FITTINGS |