Permit: T03EL00992


Addresses:

803 E ALTURAS ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/12/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
05/28/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215*/ 1) ADD A 2ND GROUND ROD. LOCATE 6' AND AWAY FROM OTHER 2) MOVE WATER PIPE BOND TO THE SHORT PIECE THAT ENTERS INTO HOUSE 3) PUT HUB SEAL IN BOTTOM OF J-BOX 4) PUT TWO PIPE STRAPS (MIN) ON RISER PIPE. 1ST ONE S/B NOT MORE THAN 8" ABOVE PANEL