Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL00952
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK TO CLEAR RE-CONNECT #172, CALLED IN TO OFFICE 9:10 AM | |
| 05/19/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* REMOVE UNTERMINATED MC CABLE IN FRONT MAIN AREA STICKING OUT OF WALL. 2.) CIRCUITS 2 & 4 HAVE DOUBLE LUGGING ON BREAKER 60 AMP AND ONE SET OF CONDUCTORS ARE #12. REMOVE OTHER DOUBLE LUGGING IN PANEL AND REMOVE ROMEX IN PANEL. REMOVE AC OR MC CABLES HANGING OUT OF CEILING BACK RM 5.) REMOVE YELLOW LOCK (CUSTOMER) AT 400 AMP MAIN DISCONNECT TO INSPECT NOT TEP LOCK. OWNER TO HAVE LICENSED ELECTRICAL CONTRACTOR TO MAKE REPAIRS PLEASE VERIFY BY LEAVING NAME ON NEXT REQUESTED INSPECTION. |