Permit: T03EL00944

Parcel: 11803393A

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T03EL00944

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
08/01/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*SENT TO TEP 0804AM
07/10/2003 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
07/03/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245* 1) GROUND RODS MUST HAVE MIN 6' SEPARATION, PER ART 250 NEC, MUST BE CONNECTED TOGETHER, AND TERMINATE AT SAME POINT. 2) INSTALL BOND BUSHING INSTEAD OF PLASTIC OR BONDING TYPE LOCKNUTS AT RISER TERMINATION, AND AT METER TERMINATIONS . PER NEC ART 250-94. 3) INSTALL PERMANENT ADDRESS LABELS ON SERVICE ENCLOSURES, SCREWED OR RIVITED, MARKING PEN NOT ACCEPTABLE/ PER #9287 CITY ORD.