Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T03EL00944
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/01/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*SENT TO TEP 0804AM | |
07/10/2003 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000* | |
07/03/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* 1) GROUND RODS MUST HAVE MIN 6' SEPARATION, PER ART 250 NEC, MUST BE CONNECTED TOGETHER, AND TERMINATE AT SAME POINT. 2) INSTALL BOND BUSHING INSTEAD OF PLASTIC OR BONDING TYPE LOCKNUTS AT RISER TERMINATION, AND AT METER TERMINATIONS . PER NEC ART 250-94. 3) INSTALL PERMANENT ADDRESS LABELS ON SERVICE ENCLOSURES, SCREWED OR RIVITED, MARKING PEN NOT ACCEPTABLE/ PER #9287 CITY ORD. |