Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 5/21/03 AT 9:15AM. | |
| 05/13/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*LOAD FEEDERS NOT ALLOWED TO PASS THRU METERING SECTION OF ENCLOSURE. 230-7 NEC. 2.) I.D. ALL CIRCUIT BREAKERS. 3.) ADDRESS TAG MUST BE SCREWED OR RIVITED TO ENCLOSURE. 4.) SERVICE ENCLOSURE INSTALLED OVER GAS METER, IN VIOLATION OF DEDICATED WROK SPACE. 110-26 NEC. NOTE THAT GAS METER WAS INSTALLED AFTER ORIGINAL SERVICE INSTALLED NEW SERVICE LOCATED WHERE OLD WAS. 2.) I.D. ALL CIRCUIT BREAKERS. 3.) ADDRESS TAG MUST BE SCREWED OR RIVITED TO ENCLOSURE. 4.) SERVICE ENCLOSURE INSTALLED OVER GAS METER, IN VIOLATION OF DEDICATED WORK SPACE. 110-26 NEC. NOTE THAT GAS METER WAS INSTALL |