Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ OK FINAL | |
| 08/04/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :PHASE ARRANGEMENT TO BE PER 384.3 MAINTAIN DEDICATED SPACE AND WORKING CLEARANCES 110-26 ALL CONDUCTORS TO BE MARKED PER 215-8 OLD UM/C TO BE SECURED TO PANEL |
|
| 01/20/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) PROPER LABELING REQUIRED-EX PANEL "A" OR "B". LABELING TO MATCH PANEL AT OTHER END. LABELING TO BE ? TO WITHSTAND ELEMENTS AND PERMANENT 2) LB COVER TO BE ACCESSIBLE 3) PLEASE UNCOVER UNDERGROUND FOR INSPECTION 4) WHERE IS LABEL ON BACK PANEL INDICATING HIGH LEG 5) WHERE ARE PLANS SHOWING NEW LOADS AND CIRCUITS THE BACK PANEL HAS A 225 AMP MAIN | |
| 07/15/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) PLEASE LABEL DISCONNECTS 2) CLEAN SURFACES UNDER LUGS 250.12 3) PLEASE PROVIDE REJECTION PINS 4) FILL UNUSED OPENING IN PANEL 5) CONNECT GROUNDING EQUIPMENT CONDUCTOR AT PANEL AND SEPARATE GROUND AND NEUTRALS | |
| 06/10/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO CLEAR INCREASE, CALL FOR FINAL ONCE CHANGE OVER COMPLETE | |
| 06/05/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) SERVICE APPROVED CLEARANCE SUBJECT TO TEP APPROVAL FOR 3 PHASE 120/208 VOLTS 2) CALL FOR FINAL ONCE CHANGE OVER COMPLETE |