Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL00871
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK TO CLEAR 2) PLEASE MOVE WHITE TAPE CLOSER TO WEATHER HEAD 3) PLEASE MOVE WHITE TAPE CLOSER TO WEATHER HEAD 3) PLEASE MOVE GAS BOND TO INTERIOR SIDE PIPING | |
| 05/30/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CANCELLED BY OFFICE | |
| 05/28/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) PLEASE LABEL ALL BREAKERS 3) USE AN APPROVED FITTING AT LB'S CHASE NIPPLE IS NOT APPROVED 4) A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 5) CONDUCTOR TO BE SUNLIGHT RESISTENT 7) PROPER SIZE JUNCTION BOX IS NEEDED FOR CONDUCTOR FILL CAPCITY 8) BOND JUNCTION BOX 9) A GAS BOND IS NEEDED |