Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* 1) RUN GROUND PANEL DONE ON SITE 2) RECALL WHEN COMPLETE | |
| 06/03/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*/ 1) SE TYPE CABLE NOT APPROVED FOR UG USE SEE ARTICLE 338 NEC. ALSO STRIPPING OFF OUTER JACKET'S IN VIOLATION OF ARTICLE 310-11 NEC 2) OK TO CAP UG CONDUIT WITH CONCRETE WHERE DEPTH CANNOT HE ACHIEVED DUE TO HARD GROUND, HOWEVER MUST BE COVERED WITH 2" MINIMUM CONCRETE 3) HOMEMADE SHEETMETAL MAIN BREAKER SECURING DEVICE NOT APPROVED MUST BE LISTED 110-3 NEC4) A RE-FEE IS ASSESED, MULIPLE INSPECTIONS WITHOUT SATISFACTORY PROGRESS. PAY RE-FEE AT 201 N. STONE, PRIOR TO FUTURE INSPECTIONS | |
| 05/30/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) NOTES: MAIN BREAKER AT PANEL BOARD AT UNIT MUST BE SECURED IN PLACE BY ADDITIONAL FASTENER. 384-16G NEC 2) NO MARKING ON CONDUCTORS USED TO FEED UNIT. AS REQUIRED BY 310.11 NEC A & B 3) U.G. CONDUIT MUST BE AT LEAST 18" BELOW GRADE. THE CURRENT DEPTH MEASURED BETWEEN 12-15" MAXIMUM SEE 300-5 NEC 4) PANEL OUTSIDE UNIT IS TOUCHING METAL WATER HEATER ENCLOSURE SEE 110-26 FOR CLEARANCE | |
| 05/28/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920* | |
| 05/13/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*U.G. CONDUIT MUST BE 18" BELOW GRADE.2.) NO COMPLIANCES WITH ITEM #2 LAST INSP. | |
| 05/08/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NO RECORD OF UNDERGROUND INSP. APPROVAL PRIOR TO BACKFILL. 2.) TYPE NM ROMEX NOT LISTED FOR UNDERGROUND USE. 3.) PREVIOUS INSP. ON UNIT BY R OHAVER T03CM01593 |