Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*OK TO CLEAR INCREASE FINAL APPROVED. | |
| 05/09/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*PERMISSES WIRING COMBINED WITH SERVICE (UTILITY) CONDUCTORS IN SERVICE RACEWAY COMPARTMENT TOP ENTRY IN THIS SQUARE D SERVICE PANEL BOARD IS IN VIOL. OF 230-7 N.E.C. 2.) MUST ERATE BRANCH CIRCUIT AND FEEDER CONDUCTOR AT TOP OF ROOF AND FUSE ACCORDINGLY WITHOUT COMPROMISING THE MINIMUM REQUIRED BRANCH CIRCUIT RATINGS. 3.) MUST HAVE THE MECHANICAL PERMIT AT SITE. |