Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 5/9/03 AT 9:15AM | |
| 04/30/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* WATERLINE SUBJACENT TO SERVICE PANEL BOARD (PVC AND SHUT OFF VALVE) IN VIOL. OF ART 110-26 N.E.C. 2.) LOCK NUT MISSING A OFFSET NIPPLE FOR GFI WEATHER PROOF BOX, SUPPORT BOX AND CONDUIT 3.) NEED PERMANENT ADDRESS TAG PER CITY AMENDMENTS. 4.) USE 1/4" HARDWARE EG. 1/4" LAG BOLTS FOR 2" IMC STRAP ON RISER. |