Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 5/21/03 @ 9:15AM | |
| 05/18/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) PLEASE FINISH ITEM # 1, 6, 7 OF PREVIOUS INSPECTION, AS DISCUSSED 2) LABEL BREAKERS | |
| 05/13/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PLEASE TIGHTEN LOCKNUTS & FITTINGS. 2.) OPEN/UNCOVER CONDUITS BURIED. 3.) LABEL METERS & PANELS AS TO ADDRESS. 4.) PLEASE PROVIDE PLANS FOR ALL NEW ELECTRIC THAT HAS BEN INSTALLED. 5.) VERIFY GAS & WATER BONDING. 6.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED AT GROUNDED TERMANAL. 7.) BREAKERS ARE TO BE LISTED FOR USE BY MANFACTURE. |
|
| 05/07/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* THIS IS NOT AN ADDITIONAL METER. THIS IS A SERVICE UPGRADE. PERMITS WILL BE NEEDED FOR BOTH SERVICES. ALSO ADD TO PERMITS FOR NEW ELECTRICAL CIRCUITS AND WIRING. SERVICE IS BEING DE ENERGIZE TO SAFTEY HAZARDS OF LIVE/EXPOSED PARTS AND INADIQUATE INSULATION OF SPLICES. THIS SERVICE IS NOT READY FOR INSPECTION FINISH BONDING, SEALING, AND TERMANATIONS. |