Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/02/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 5/5/03 AT 9:15AM OK TO CLEAR
04/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) SUPPORT 3/4" CONDUIT PER 348-13 NEC.
2.) USE OF 1/2" EMT CONNECTOR FOR CLOSE NIPPLE AT 1/2" LB NOT APPROVED.
3.) USE SEALING LOCKNUT AT TOP PENNETRATION OF PANEL.
4.) USE GROUND BUSHING AT 3/4 CONCENTRIC. KO.
5.) I.D. ALL CIRCUIT BREAKERS.