Permit: T03EL00760

Parcel: 11105229A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/08/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) LOCKED RESIDENCE NEEDS TO BE OPEN FOR INSPECTION.
2.) OPEN SPLICED WIRE AT OUTSIDE N. WEST CORNER NEEDS TO BE CORRECTED ALL SPLICES NEED TO BE IN BOX.
3.) REAR OUTDOOR PORCH LIGHT MISSING MUST BE INSTALLED AND REMOVE UN USED ROMEX WIRING IN PORCH AREA
4.) REMOVE UN USED WIRING AT REAR STORAGE ROOMS.
5.) INSTALL AN ADDRESS LABEL ON SERVICE (PERMANENT ONE).
6.) THE 200 AMP MAIN CIRCUIT BREAKER IN SERVICE THE HANDLE TO TURN OFF AND ON IS BROKEN.