Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/23/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) LOCKED RESIDENCE NEEDS TO BE OPEN FOR INSPECTION. 2.) OPEN SPLICED WIRE AT OUTSIDE N. WEST CORNER NEEDS TO BE CORRECTED ALL SPLICES NEED TO BE IN BOX. 3.) REAR OUTDOOR PORCH LIGHT MISSING MUST BE INSTALLED AND REMOVE UN USED ROMEX WIRING IN PORCH AREA 4.) REMOVE UN USED WIRING AT REAR STORAGE ROOMS. 5.) INSTALL AN ADDRESS LABEL ON SERVICE (PERMANENT ONE). 6.) THE 200 AMP MAIN CIRCUIT BREAKER IN SERVICE THE HANDLE TO TURN OFF AND ON IS BROKEN. 7.) CANNOT VERIFY GROUNDING SYSTEM TO SERVICE IF IT CANNOT BE VERIFIED AS TO WHAT IT CONNECTS TO MAY NEED TO INSTALL NEW SYSTEM (PLEASE DIG UP END) 8.) ONCE INSIDE INSPECTION DONE WILL NEED TO SEE ALL LIGHTS CONNECTED, ALL SWITCHES AND COVERS FOR RECEPTACLES INSTALLED, SMOKE DETECTORS IN BEDROOMS, BATTERY OK. PLS RECALL AND HAVE OPEN. |