| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 04/30/2003 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 5/1/03 AT 9:15AM OK CABLE DROP OK TO CLEAR TEMP SERVICE. 1.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSER, MUST BE SCREWED OR RIVITED. 2.) INSTALL W/P J-BOX FOR SUB PANEL SPLICES, AND GROUND. 3.) BOND GAS PIPING. 4.) SUPPORT RISER. NOTE THAT TEMP POWER AND CABLE DROP WILL ALLOW THE OWNER TO COMPLETE WORK ON SERVICE, DUE TO ROOFING INSTALL. |