Permit: T03EL00733

Parcel: 121064040


Addresses:

5739 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/23/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 4/24/03 AT 9:15AM OK TO CLEAR RE CONN.
04/22/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) FINISH #2 OF PREVIOUS INSPECTION. ALL DEVICES IF OVER 1/4" IN NON COMBUSTABLES AND FLUSH FOR COMBUSTABLES 370-20.
2.) CLOCK OUTLET NEEDS A BOX OR REMOVE.
04/18/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FINISH ITEMS #1 & 2 OF PREVIOUS INSPECTION METAL RINGS ARE NOT APPROVED.
04/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) we have grounded receptacle on an ungrounded cable (nm).
2.) approved extender rings are needed to protect from combustable.
3.) termanate nm cable ground
4.) use approved splicing methods in junction boxes.
5.) a licensed l-11 electrical contractor to perform work.