Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 4/24/03 AT 9:15AM OK TO CLEAR RE CONN. | |
| 04/22/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) FINISH #2 OF PREVIOUS INSPECTION. ALL DEVICES IF OVER 1/4" IN NON COMBUSTABLES AND FLUSH FOR COMBUSTABLES 370-20. 2.) CLOCK OUTLET NEEDS A BOX OR REMOVE. |
|
| 04/18/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*FINISH ITEMS #1 & 2 OF PREVIOUS INSPECTION METAL RINGS ARE NOT APPROVED. | |
| 04/17/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) we have grounded receptacle on an ungrounded cable (nm). 2.) approved extender rings are needed to protect from combustable. 3.) termanate nm cable ground 4.) use approved splicing methods in junction boxes. 5.) a licensed l-11 electrical contractor to perform work. |