Permit: T03EL00731

Parcel: 126210490

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL00731

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 5/9/03 AT 9:15AM ALL UNDERGROUND IS 24' & CANNOT USE ELECTRICAL UNTIL NEW PERMITTED OBTAINED.
04/30/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*ITEMS FOREIGN TO THE ELECTRICAL SUBJACENT
TO THE SERVICE PANEL BOARD IS VIOLATING 199 N.E.C. 110-26.
WATER LINE AND T.V. CONDUITS TO BE REMOVED.
SUPPORT 3/4" EMT CONDUIT AT SIDE OF BOX.
120 (1/2 WAY) 240 FT OF PVC CONDUIT VERIFIED AS TO MINIMUM CODE STANDARDS. PLEASE HAVE APPROVED CITY PLAN DETAILING PERMITTED INSTALLATION BEFORE NEXT INSPECTION, BEFORE C/D AND SERVICE CLEARANCE. CROSS REFERENCE IS MORE LIKE 300S.