Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2003 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 04/24/2003 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 4/25/03 AT 9:15AM OK TO CLEAR TEMP SERVICE OK CABLE DROP. | |
| 04/22/2003 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*PLEASE FINISH ITEMS 2,7 & 8 OF PREVIOUS INSPECTION. | |
| 04/18/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* ACORN CLAMP LISTED FOR ONLY ONE CONDUCTOR. 2.) A BONDING DEVICES IS NEED FOR RISER. 3.) ADDRESS LABEL IS TO BE SCREWED OR RIVITED TO COVER. 4.) CLEAN PAINT SURFACE UNDER GAS BOND CLAMP. 5.) BOND TO INTERIOR SIDE OF WATER VALVE. 6.) STRAP GROUNDING CONDUCTOR TO STRUCTURE. 7.) PLEASE VERIFY PERMIT FOR 2ND STRUCTURE. 8.) PLEASE LEAVE INSPECTION CARD ON SITE. |