Permit: T03EL00677

Parcel: 132160130


Addresses:

1551 E BENSON HY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL00677

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) ARRIVED AT 12:15 PM FOREMAN NOT ON SITE. OK CABLE DROP-(51) M.H. PEDESTAL. NOTE: THAT CABLE DROP AND CONNECTIONS ALREADY DONE BY TEP
06/20/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) INSTALL PERMANENT ADDRESS OR LOT NUMBERS ON PEDISTALS, SCREWED OR RIVITED TO ENCLOSURE. 2) REMOVE COVERS TO ALL PEDISTALS FOR INSPECTION TOO MANY FOR INSPECTION TO UNCOVER (31) PEDISTALS
05/08/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
CABLE DROPS INSTALLED PRIOR TO C.O.T. APPROVAL
2.) GROUNDING ELECTRODE CONDUCTOR NOT CONNECTED PROPERLY. SHOULD BE CONNECTED AT POINT OF GROUNDED CONDUCTOR SERVICE CONNECTION WITHIN PEDISTAL PER ART 250-24
SHOULD BE UNSPLICED.
3.) NOTE THAT TEP PERSONAL MADE THE GROUNDING ELECTRODE CONNECTION TO PEDISTALL, GROUND RODS BY OWNER.