Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) ARRIVED AT 12:15 PM FOREMAN NOT ON SITE. OK CABLE DROP-(51) M.H. PEDESTAL. NOTE: THAT CABLE DROP AND CONNECTIONS ALREADY DONE BY TEP | |
| 06/20/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) INSTALL PERMANENT ADDRESS OR LOT NUMBERS ON PEDISTALS, SCREWED OR RIVITED TO ENCLOSURE. 2) REMOVE COVERS TO ALL PEDISTALS FOR INSPECTION TOO MANY FOR INSPECTION TO UNCOVER (31) PEDISTALS | |
| 05/08/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* CABLE DROPS INSTALLED PRIOR TO C.O.T. APPROVAL 2.) GROUNDING ELECTRODE CONDUCTOR NOT CONNECTED PROPERLY. SHOULD BE CONNECTED AT POINT OF GROUNDED CONDUCTOR SERVICE CONNECTION WITHIN PEDISTAL PER ART 250-24 SHOULD BE UNSPLICED. 3.) NOTE THAT TEP PERSONAL MADE THE GROUNDING ELECTRODE CONNECTION TO PEDISTALL, GROUND RODS BY OWNER. |