Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ NICE JOB. LOOKS GOOD. |
| 10/29/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK RECEPTS. AROUND PLAZA |
| 09/23/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) NOTES: PERIMETER FENCE SECURITY LTG. SUPPORT PVC FROM GROUND TO J-BOX 2) SUPPORT J-BOXES AT LIGHT FIXTURES, PER NEC 3) SEAL FIXTURE TO BOX TO MAKE RAIN TITE 4) USE PROVIDED GROUND SCREW TO GROUND ALL FIXTURE J-BOXES |
| 09/11/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 09/08/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TO CLEAR PEDESTAL FOR SPACE #25 2) PROVIDE BOND BUSHING IN WELL SERVICE PER 250 94 THRU 96 SENT TO TEP ON 0909AM |