Permit: T03EL00669

Parcel: 132160130


Addresses:

1551 E BENSON HY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL00669

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/21/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ NICE JOB. LOOKS GOOD.
10/29/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK RECEPTS. AROUND PLAZA
09/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) NOTES: PERIMETER FENCE SECURITY LTG. SUPPORT PVC FROM GROUND TO J-BOX 2) SUPPORT J-BOXES AT LIGHT FIXTURES, PER NEC 3) SEAL FIXTURE TO BOX TO MAKE RAIN TITE 4) USE PROVIDED GROUND SCREW TO GROUND ALL FIXTURE J-BOXES
09/11/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
09/08/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK TO CLEAR PEDESTAL FOR SPACE #25 2) PROVIDE BOND BUSHING IN WELL SERVICE PER 250 94 THRU 96 SENT TO TEP ON 0909AM