Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 4/21/03 AT 9:15AM. | |
| 04/16/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*COMPLETE #2 OF PREVIOUS INSPECTION AND WE NEED ACCESS TO LOOK AT #5 OF PREVIOUS INSPECTION. | |
| 04/08/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRYING PARTS. 2.) INSTALL GROUNDS AS PER MANUFACTURES LABELING AND DOSE APPROVED GROUNDING CONNECTORS. 3.) MAINTAIN BENDING RADIUS ON CONDUCTOR. 4.) ANTIOXIDE COMPOUND IS NEEDED FOR ALUMINIUM TERMANATIONS. 5.) STRAP NM CABLE AND PROTECT WHERE NEEDED. |