Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 04/03/2003 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*PLEASE COMPLY W/NEC 250-64 (E). METALIC PROTECTION INSTALLED REQUIRER PROPER GROUND FITTING @ END OF CONDUITS THANKS PLEASE RECALL. |
|
| 04/02/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*1.) PLEASE USE #4 GRND. WIRE IF NO PHYSICAL PROTECTION WILL BE AFFORDED FOR GROUND WIRE. 2.) INSTALL A SECOND GROUND ROD. 3.) USE PROPER FITTING TO TERMINATE SLB. INTO SERVICE PANEL. 4.) MSUT USE PERMANENT METAL TAG FOR ADDRESS ATTACH W/SCREWS OR RIVETS PLEASE RECALL INSPECTIONS. |