Permit: T03EL00608

Parcel: 134242520


Addresses:

1041 S ELI DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/07/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
04/03/2003 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*PLEASE COMPLY W/NEC 250-64 (E).
METALIC PROTECTION INSTALLED REQUIRER PROPER GROUND FITTING @ END OF CONDUITS THANKS PLEASE RECALL.
04/02/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) PLEASE USE #4 GRND. WIRE IF NO PHYSICAL PROTECTION WILL BE AFFORDED FOR GROUND WIRE.
2.) INSTALL A SECOND GROUND ROD.
3.) USE PROPER FITTING TO TERMINATE SLB. INTO SERVICE PANEL.
4.) MSUT USE PERMANENT METAL TAG FOR ADDRESS ATTACH W/SCREWS OR RIVETS PLEASE RECALL INSPECTIONS.