Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL00594

Parcel: 112071730


Addresses:

2550 N TUCSON BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - FINAL Approved CORRECTIONS NOTED 04/03/2003 ARE OK. FINAL MAKE UP OK
04/07/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO CLEAR SERVICE UPGRADE.SENT TO TEP ON 4/8/03 AT 9:15AM
04/03/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED TERMANAL. 250-24.
2.) MISSING DEAD FRONT COVERS AND PANEL LABELING.
3.) FUSES AND "R" PIN TO E INSTALLED.
04/01/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*BONDING DEVICES NEEDED AT ALL POINTS BEFORE 1ST DISCONNECTING MEAN AT SERVICE 250-94.
2.) BONDING JUMPER TO BE SIZED PER 250-102 & 250-66.
3.) DE RATE CONDUCTORS IN RACE WAY OVER 24" AR PER 310-15.