Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2008 | ELECTRIC - FINAL | Approved | CORRECTIONS NOTED 04/03/2003 ARE OK. FINAL MAKE UP OK | |
| 04/07/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR SERVICE UPGRADE.SENT TO TEP ON 4/8/03 AT 9:15AM | |
| 04/03/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED TERMANAL. 250-24. 2.) MISSING DEAD FRONT COVERS AND PANEL LABELING. 3.) FUSES AND "R" PIN TO E INSTALLED. |
|
| 04/01/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*BONDING DEVICES NEEDED AT ALL POINTS BEFORE 1ST DISCONNECTING MEAN AT SERVICE 250-94. 2.) BONDING JUMPER TO BE SIZED PER 250-102 & 250-66. 3.) DE RATE CONDUCTORS IN RACE WAY OVER 24" AR PER 310-15. |