Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR. SENT TO TEP ON 4/22/03 | |
| 04/16/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*FINISH ITEMS #2 & 5 OF PREVIOUS INSPECTION AND VERIFY PERMIT FOR INTERIOR WORK. | |
| 03/28/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) A PERMANENT METAL ADDRESS LABEL IS NEEDED. 2.) MAINTAIN WORKING CLEARENCE AT SERVICE 110-26 (GAS PIPING.) 3.) PLEASE VERIFY WTER BONDING. 4.) WE HAVE MULTIPOLE TERMANATIONS AT GROUND LUG 110-14. 5.) TIGHTEN LOOSE FITTINGS. 6.) PLEASE SECURLY ATTACH PANEL TO STRUCTURE. 7.) RISER HARDWARE TO BE 1/4" MINIMUM. 8.) WE ARE MISSING HARDWARES FOR LB. 9.) PLEASE BOND AROUND GAS UNION TO MAINTAIN INTERIOR PIPING BONDS. 250-104. 10.) MAINTAIN CONDUCTOR CLEARENCES ABOVE DOOR 230-24. PLEASE VERIFY PERMITS FOR WORK NEW BEING DONE TO INTERIOR. |