Permit Number - T03EL00578

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/03/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) SET SCREW CONNECTORS AND COMPLINGS NOT RATED FOR OUTDOOR USE.
2.) 30 AMP CIRCUITS FEEDING 20AMP RECEPTACLES.
3.) #10 WIRE IS STRANDED CANNOT WRAP AROUND SCREWS.
4.) J-BOX NEEDS BUSHING WHERE WIRE COMES INTO BOX.
5.) RECEPTACLE USING NEUTRAL ON GROUNDED RECEPTACLE.