Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL00578
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
04/03/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) SET SCREW CONNECTORS AND COMPLINGS NOT RATED FOR OUTDOOR USE. 2.) 30 AMP CIRCUITS FEEDING 20AMP RECEPTACLES. 3.) #10 WIRE IS STRANDED CANNOT WRAP AROUND SCREWS. 4.) J-BOX NEEDS BUSHING WHERE WIRE COMES INTO BOX. 5.) RECEPTACLE USING NEUTRAL ON GROUNDED RECEPTACLE. |