Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/24/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FINAL. |
| 06/11/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WE HAVE MULTIPLE TERMANATIONS AT GROUND LUG 110.14 2) CANNOT STACK LUGS AND CLEAN SURFACE UNDER LUGS 250.12 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 4) PLEASE IDENTIFY NEUTRAL AT TERMINAL 200-6 |