Permit: T03EL00575

Parcel: 13315304B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/24/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ OK FINAL.
06/11/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) WE HAVE MULTIPLE TERMANATIONS AT GROUND LUG 110.14 2) CANNOT STACK LUGS AND CLEAN SURFACE UNDER LUGS 250.12 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 4) PLEASE IDENTIFY NEUTRAL AT TERMINAL 200-6